Load impedance: 0 to 720 Ohms
Output range: 4-20mA, (3.5mA error)
Galvanic isolation: none
Wiring Option (A)
- Connect positive terminal of current input module to desired channel terminal of SME device
- Connective negative terminal of current input module to negative power supply terminal used for SME device
Wiring Option (B)
- Connect positive terminal of current input module to desired channel terminal of SME device
- Connective negative terminal of current input module to V- terminal of SME device
Notes
- The 4/20mA outputs are not galvanically isolated. It is not recommended to route the 4/20mA to off-site locations if the corresponding 4/20mA input does not provide galvanic isolation.
- Only for Ex Sensors. Power Input: 240V Maximum AC Single Phase, this is exclusive for Ex sensor configuration and would be the best to protect the zener barriers used in the configuration, only single phase power supplies should be used.
References: