SRV EX Installation without temperature
The SRV can be used without a temperature connection to the electronics. Operation of sensor does not depend on the temperature and hence a temperature input is not required.
the SRD needs temperature input to the electronics so either the temperature sensor built in the sensor is used or an external Pt1000 can be connected to sensor electronics. It is also possible to write temperature of the sensor from an external probe over Modbus.
This article focuses on using SRV without a temperature connection. This could be the case when the EX barriers that are needed for Pt1000 are not available or the customer does not want to use 2 additional barriers that are needed for the Pt1000 connection.
Ex Installation diagram without temperature
The figure below shows the diagram for the connection. It is taken from the EX installation manual (Figure 10 from Manual version 2.0 of manual).
1 | M12 cable connector female, rear view |
2 | Sensor:M12 connector male, front view |
3 | Ground tab (optional) |
A | Safe Zone |
B | Intrinsically safe cable |
C | Hazardous Zone |
Zener barrier specification
The Zener diode barrier connected to the transducer coil circuit must meet the following specifications (Table 4 from EX installation manual version 2.0):
Transducer coil circuit Zener diode barrier specifications
Max. output voltage | Uo | < 7.3 | V |
Min. series resistance | Ro | > 9.8 | Ohm |
Max. output current | Io | < 730 | mA |
Max. output power | Po | < 1.3 | W |
Fuse rating |
| <=200 | mA |
This Zener diode barrier must have two channels, one for each conductor of the transducer coil circuit.
Commercial Zener diode barriers that fulfill these specifications are inTable 6 from EX installation manual version 2.0:
For transducer coil circuit:
- Pepperl + Fuchs Z757
Specification of commercial Zener diode barrier suitable for transducer coil circuit
Series resistance | 9.8 ohms, min. |
Fuse rating | 200 mA |
Maximum safe voltage | 250 V |
Output voltage, Uo | 7.14 V |
Output current, Io | 729 mA |
Output power, Po | 1.3W |
Notes on temperature output
Even though there is no direct measurement of temperature from the probe when the temperature leads from the probe are not connected to the electronics, the sensor does estimate a process temperature based on the frequency characteristics of the sensor. This estimated temperature is only to be used as a guide as it can be influenced by deposits. This estimated temperature replaces the measured temperature in the output strings of the sensor so you will still see a temperature output from the sensor.
Note:
|
Reference
Rheonics EX installation manual: https://rheonics.com/resources/manuals/
Article: Is it still possible to measure viscosity without connecting the PT1000 to our SRV?