Modbus RTU (RS-485)
General All SME devices implement a MODBUS RTU compliant RTU slave. The default configuration of the MODBUS RTU slave is 38400 and ODD parity. Connec...
Thu, 8 Jul, 2021 at 5:28 PM
The table uses PDU addressing; addresses start at zero. Depending on the PLC used it might be required to add 1 to the addresses in the table below. Mod...
Mon, 11 Sep, 2023 at 3:30 PM
Float: IEEE754 floating point. This data type spans two registers which should be read together. Depending on the endianness of the host it might be necess...
Fri, 3 Jul, 2020 at 2:03 PM
Reading the parameter 3, Temperature median, in float data type, from the SMET Device Address= 01 = 0x01 (byte). Address 40057-40001=56 = 0x0038 (word) ...
Fri, 3 Jul, 2020 at 3:34 PM
ModbusPoll is a commercially available software from Witte GmbH. 1. Intro to Modbus RTU on Rheonics SME All SME devices implement a MODBUS RTU-compliant ...
Thu, 30 Nov, 2023 at 12:13 AM
1.MODBUS RTU TROUBLESHOOTING 1.1.Verify the Baud Rate, Stop Bits, Data Bits and Parity. Factory default settings of Modbus parameters: address=1 baud...
Tue, 2 Nov, 2021 at 3:16 AM
Modbus RTU is available on Rheonics process density meters and viscometers over a 2-wire RS-485 interface. The device does not have internal biasing resisto...
Thu, 7 Dec, 2023 at 11:13 PM