SME Electronics

Connecting and disconnecting wires to the terminal blocks on SME electronics
The wires are generally color coded, the ends should be crimped with 8mm diameter crimps. This connection is valid for sensor cable, power cable, Modbus ...
Fri, 3 Jul, 2020 at 1:44 PM
Connecting sensor cable colored wires to transmitter electronics
The sensor is connected to the transmitter electronics by a sensor cable. Follow the color code table below to connect the correct wires from the sensor cab...
Fri, 3 Jul, 2020 at 3:40 PM
Powering the Sensor - Input power to transmitter
1. Sensor Power Consumption Voltage required: 24V DC Voltage range acceptable: 18-36V DC Current required (min): 120 mA Power required (maximum)...
Tue, 15 Aug, 2023 at 11:50 PM
Transmitter Display Module installation instructions (SME-TRD)
The picture below shows the SME-TRD.    Open the Red display cover by rotating it anti-clockwise.    Now carefully pull out the display mod...
Fri, 3 Jul, 2020 at 6:43 PM
USB Connection to the Transmitter
If you have ordered the USB connection then you will receive the unit with a USB adapter board as shown in picture below.     To connect the USB cable, ta...
Fri, 3 Jul, 2020 at 5:26 PM
Electromagnetic Compatibility Tests for Sensor Probe and Electronics
What EMC standards do the SME electronics (SME-DRM, SME-TR/D) and sensor probes (SRV, SRD, DVP, DVM) conform with? Rheonics Sensor transducers and elect...
Fri, 28 Aug, 2020 at 5:31 PM
Sensor electronics (SME) - Wiring drawing
Rheonics sensor electronics is the brain of the sensor probe. In addition, it supports multiple communication options. The figure below shows the typical c...
Tue, 15 Aug, 2023 at 11:54 PM
SME-Drawings
What products are involved? The SME - Sensor module electronics that is used for all Rheonics sensors. What is the purpose of this article? To show the SME...
Wed, 15 May, 2024 at 5:13 PM